Construction Japanese · Structural & Core Works
What does 耐火被覆 mean in Japanese?
Fireproofing (structural steel fire protection)
| Terms | 耐火被覆 |
|---|---|
| Reading | たいかひふく |
| English Meaning | Fireproofing (structural steel fire protection) |
| Level | Advanced |
| Specialty Area | Structural & Core Works |
| Specialty | Construction Japanese |
Technical Explanation
Protective thermal insulation applied around structural steel columns and beams to prevent them from softening rapidly during a building fire—bare steel loses yield strength at elevated temperatures. Typically applied by spray-applying rockwool (ロックウール吹付け) or installing calcium silicate board encasements. Thicknesses correspond to statutory fire-resistance hours and must be surveyed upon completion.
Practical Notes
MEP hanger rods and cable tray supports should be anchored to structural steel before fireproofing is applied; installing attachments afterward tears open the coating, leaving patching defects commonly cited by inspectors.
Workplace Examples
耐火被覆を吹き付ける前に、設備の吊りボルトを付けておいてください。
Before spray-applying fireproofing, please install the MEP hanger bolts in advance.